A second short dead-link outage within 5 min of an early trial holds the inverter's forced mode up to 5 min #1934

Open

Description

@frahlg

Follow-up from #1909 (owner decision, 28 Oct 2026: same as master, fix after stable).

When a battery comes back from an outage, #1909 gives it one early trial of its default mode. If a second short dead-link outage (under the 60 s watchdog) starts within 5 min of that trial, before the battery command was accepted, Core cannot tell it apart from a device that refuses commands on a flaky link. It then waits out the 5 min refusal window, and the inverter can hold its last forced command for up to 5 min.

Making this case return early today would bring back a default and a trial after every failed read for a device that truly refuses (TestDriverRefusingOnFlakyLinkGetsOneEarlyTrial). A second signal is needed, for example the length of the failed-read run.

Test: the reviewer's TestReviewSecondDeadLinkOutageAfterReturn with a 1 min idle gap: the default goes out within 10 s of the second return, while the flaky-link test still gives 1 trial and 2 defaults in 5 min.

🤖 Generated with Claude Code